Why reactive penalties occur
Inductive loads such as motors, transformers and ballasts draw reactive power that does no useful work. A compensation system balances it with capacitors. If it under-compensates, inductive limits are exceeded; if it over-compensates, capacitive limits are exceeded, and the distribution company bills the excess.
Limits
- Facilities up to 50 kW: inductive 33%, capacitive 20%
- Above 50 kW: inductive 20%, capacitive 15%
- Compensation is mandatory above 50 kW
Ratios are calculated against active consumption and may be updated by regulation.
Most common causes
- Degraded or failed capacitors
- Faulty contactors and fuses
- Incorrect reactive power controller settings (CT ratio, target cosφ)
- Compensation not expanded as the facility grew
- Harmonics rapidly damaging capacitors
- Capacitive excess at low night or weekend loads
Step-by-step solution
- Review the inductive/capacitive ratios of recent months
- Check capacitors, contactors and fuses in the panel
- Verify controller settings and CT connection
- Measure load profile and harmonics with a power analyser if needed
- Add steps, a shunt reactor or a detuned/filter solution accordingly
- Put the system on a periodic maintenance plan
Professional support
PF Endüstri provides reactive penalty analysis, compensation design, installation and periodic maintenance. Send us your bills and facility details and we will assess the situation together.