Transformer Maintenance and Testing

The transformer is the heart of your power system. Regularly tested and maintained transformers last longer and are less likely to fail unexpectedly. Our specialist team measures, reports and clearly shows what action needs to be taken.

Power transformer under maintenance

Maintenance interval

Transformers and other HV equipment should be visually inspected every month by the HV operation manager, with comprehensive periodic maintenance at least once a year. Maintenance prevents both power quality problems and safety incidents.

Checks carried out

  • Locating and fixing oil leaks
  • Cleaning external surfaces
  • Tank paint and mechanical checks
  • Bushing inspection and replacement of cracked bushings
  • Silica gel check and replacement
  • Arcing horn inspection and adjustment
  • Tightness check of connections
  • Oil level, thermometer, Buchholz and hermetic relay function tests
  • Earthing connection check and measurement
  • Oil top-up
  • Tap position check; on-load tap changer maintenance

Measurements

Insulation resistance (megger test)

Determines winding-to-earth and winding-to-winding insulation and sets a reference for future measurements.

Winding resistance

Checks windings and terminal connections and reveals tap changer problems.

Earthing resistance

Protection and system earthing values are tracked so that protective devices can detect fault currents.

Turns ratio (TTR test)

Measures the ratio between HV and LV windings and reveals short circuits and open circuits.

Transformer oil analysis

A transformer's life depends largely on its oil. In annual maintenance we perform the following tests and recommend corrective action where needed:

  • Breakdown voltage: low values indicate water, dirt and particles
  • Power factor: high values indicate contamination and oxidation
  • Colour and appearance: clean and clear oil is expected
  • Acidity: high values indicate oxidation and corrosion risk
  • Water content: directly affects insulation and dielectric strength

Where needed, oil treatment removes particles and moisture and restores dielectric strength.

24/7 transformer service

Our fault/service team is available 24/7 for faults in your HV and MV installation, responding on site with professional test equipment under the lead of a responsible electrical engineer.

Frequently asked questions

How often should a transformer be maintained?

At least once a year comprehensively, with monthly visual checks by the HV operation manager.

Why is oil analysis necessary?

Water, dirt and oxidation in the oil weaken insulation. Breakdown voltage, acidity and water content tests reveal problems before failure.

How fast can you respond to an emergency?

Our service team works 24/7 and reaches sites in Izmir and neighbouring provinces as quickly as possible.

Your quote within 24 hours

Attach your single-line diagram or project and one of our engineers will call you.

Chat on WhatsApp
We only use essential cookies and anonymous statistics.
Details