What is compensation?
Industrial facilities, especially those with many motors, draw reactive power in addition to active power. This power does no useful work but loads networks, cables and switchgear, forcing larger equipment and higher costs.
A compensation system measures the varying reactive load with a reactive power controller and switches capacitor steps to minimise it. Under-compensation loads the grid inductively, over-compensation capacitively; both are undesirable.
Reactive consumption limits in Turkey
- Facilities of 9 kW and above must limit reactive consumption; compensation is mandatory above 50 kW.
- Up to 50 kW: inductive consumption must not exceed 33% and capacitive 20% of active consumption.
- Above 50 kW: inductive consumption must not exceed 20% and capacitive 15% of active consumption.
- If limits are exceeded, the distribution company adds reactive charges to the bill.
Limits may be updated by regulation; we assess your facility against the current rules.
Our services
- Reactive/capacitive penalty analysis and consultancy
- Compensation design and installation
- Harmonic measurement and detuned/filter solutions
- Compensation panel maintenance, capacitor and contactor checks
- Reactive power controller setting and testing
Frequently asked questions
Why do reactive penalties occur?
If the system under-compensates, inductive limits are exceeded; if it over-compensates, capacitive limits are exceeded, and the distribution company bills the excess.
Is compensation mandatory?
Yes, for facilities with an installed power above 50 kW.