What is cathodic protection?
Corrosion is the deterioration of metals through chemical and electrochemical reactions with their environment; in air, water and soil it is driven mainly by oxygen diffusion.
Cathodic protection protects metal structures electrochemically within their electrolyte: a more active metal such as magnesium is sacrificed as an anode, or the protected structure is made the cathode, reversing the corrosion cell.
How is it measured?
Galvanic-anode systems require four basic measurements: structure-to-soil potential, anode-to-soil potential, tank (cathode)-to-soil potential and anode current, using copper/copper-sulphate, silver/silver-chloride or zinc reference electrodes and calibrated meters.
- Structure-to-soil potential: not below 850 mV
- Anode-to-soil potential: 1100–1700 mV
- Tank (cathode)-to-soil potential: 450–550 mV
- Anode-to-cathode current: 10–100 mA
If values are out of range, our report clearly states the corrective action: anode replacement, additional anodes or cable/connection repair.
Measurement interval
Galvanic-anode systems are easy to operate; measurement four times a year (once per season) is recommended.
Where is it used?
- Natural gas, fuel and water pipelines
- Fuel depots and filling stations
- Port and bridge structures in sea and fresh water
- Water storage tanks
We work in accordance with the Work Equipment Health and Safety Regulation, TS EN 13509 and TS EN 12954.
Frequently asked questions
How often should cathodic protection be measured?
For galvanic-anode systems, four times a year, once per season.
Is it required for fuel stations?
Facilities with underground tanks and pipelines are expected to have cathodic protection and to check it periodically under the relevant regulations and standards.